Performance/Safety Related Concern for System Sensor Low Frequency Fire Alarm Sounder

  • Type of Notification: Performance Related Concern
  • FM Approval Status: FM Approved

FM Approvals has been made aware of a quality issue in certain Low Frequency Fire Alarm Sounders that could result in low volume sound or no sound.

Company Identity: System Sensor

Address: 3825 Ohio Avenue
St. Charles, IL 60174
USA

Contact Information: LFSounder.recall@systemsensor.com

Product Identity: HWL-LF, HWL-LF-BP10, HRL-LF, HRL-LF-BP10, HGWL-LF-BP10, P2WL-LF.

Description: Low Frequency Sounders

FM Approval Status: All models bearing the FM certification mark.

Hazard Involved: System Sensor has determined that due to an electronic component quality problem, the potential exists for low volume sound output or no sound output on the models listed above with date codes 3034 and 3035 (corresponding to shipment dates of March 20, 2023 to April 3, 2023). For the P2WL-LF, this issue does not impact the products ability to flash but does impact the sound output.

System Sensor has identified an issue that could affect the sound output on the Products with date codes 3034 and 3035. Even if an issue was not identified at the time of commissioning, this notification is a safety issue and should be addressed promptly and the product replaced to avoid potential problems with system operations which may occur.

System Sensor has registered the situation with the Consumer Product Safety Commission (CPSC)

Honeywell Recalls System Sensor L-Series Low Frequency Fire Alarm Sounders and Strobes Due to Risk of Failure to Alert Consumers to a Fire | CPSC.gov

USING THIS PRODUCT?

If you suspect you are in possession of one of the affected System Sensor – Low Frequency Alarm Sounders, please follow the process indicated in the CPSC Recall Notice and attached Safety Bulletin No. SSR24.1SB.