Product Safety Notification for Micropack (Engineering) Ltd. for a potential safety concern involving their Model FDS300 and FDS301 Optical Flame Detectors and FS301 Flame Simulators
- Type of Notification: Product Safety Notification
- FM Approval Status: FM Approved
Micropack (Engineering) Ltd has notified FM Approvals of a potential safety concern involving their Model FS300 and FDS301 Optical Flame Detectors and FDS301 Flame Simulators manufactured between July 2012 and July 2019.
Company Identity: Micropack (Engineering) Ltd
Address: School Hill, Portlethen, Aberdeen, AB12 4RR, United Kingdom
Contact Information: Customer Support:
Phone Number +44 1224 784055.
Email Info@micropack.co.uk
Product Identity:
Micropack (Engineering) Ltd Models FDS300 and FDS301 Optical Flame Detectors and Model FS301 Flame Simulator
Consilium Marine & Safety AB Models CD-F 300 and CD-F 301 Optical Flame Detectors and Model CD-FS 301 Flame Simulator
Dräger Safety UK Ltd Models Flame 3000 and Flame 5000 Optical Flame Detectors and Model FS5000 Flame Simulator
Description:
he Models FDS300, CD-F 300 and Flame 3000 Optical Flame Detectors are monochrome imaging-based flame detector.
The Models FDS301, CD-F 301 and Flame 5000 Optical Flame Detectors are color imaging-based flame detector.
The Models FS301, CD-FS 301 and FS5000 Flame Simulator are used to test the correct operation of the Flame Detectors.
Nameplate Data:
Micropack (Engineering) Ltd Models FDS300 and FDS301
Consilium Marine & Safety AB Models CD-F 300 and CD-F 301
Dräger Safety UK Ltd Models Flame 3000 and Flame 5000 Flame Detectors
US
Class I, Division 1, Groups B, C and D T4
Class I, Zone 1, AEx db IIC T4
Type 4X / IP66
Ta = -60°C to +85°C (-76°F to +185°F)
Canada
Class I, Division 1, Groups B, C and D T4
Class I, Zone 1, Ex db IIC T4
Type 4X / IP66
Ta = -60°C to +85°C (-76°F to +185°F)
ATEX
II 2 G Ex db IIC T4 Ta=-60°C to +85ºC IP66
IECEx
Ex db IIC T4 Ta=-60°C to +85ºC IP66
Micropack (Engineering) Ltd Model FS301
Consilium Marine & Safety AB Model CD-FS 301
Dräger Safety UK Ltd Model FS5000 Flame Simulators
ATEX
II 2 (2) G Ex db [op is T6 Gb]
IIC T6 Gb Ta = -10°C to +50°C IP66
FM Approval Status: FM Approved
Hazard Involved: Micropack (Engineering) Ltd shipped non-conforming Micropack (Engineering) Ltd Models FDS300 and FDS301 Optical Flame Detectors, Consilium Marine & Safety AB Models CD-F 300 and CD-F 301 Optical Flame Detectors, Dräger Safety UK Ltd Models Flame 3000 and Flame 5000 Optical Flame Detectors, Micropack (Engineering) Ltd Model FS301 Flame Simulator, Consilium Marine & Safety AB Model CD-FS 301 Flame Simulator, and Dräger Safety UK Ltd Model FS5000 Flame Simulators manufactured between July 2012 and July 2019.
Due to a dimensional issue with the glass window in the assembly of the flame detectors and flame simulator, the resulting flame-path gaps do not meet the requirements of IEC 60079-1 for IIC applications and FM 3615 Class 1 DIV 1 Groups B, C and D applications. This is a safety related non-conformance that could present a dangerous situation in certain applications of the product.
Micropack (Engineering) Ltd, Consilium Marine & Safety AB and Dräger Safety UK Ltd are reaching out to all users to notify them of this situation (see attached Product Safety Notifications).
Using This Product?
If you suspect you are in possession of affected equipment bearing the FM Approvals certification marking, please bring that to the attention of:
Antonio Pires
Norwood, MA, United States
+1 (1) 781-255-4825